Mesa de exportação +86 153 1544 9600 sqr.jiuzhouge@gmail.com Mon–Sat 08:30–18:00 (GMT+8)

DFN · GFN (L / DP / GP basin options) · VFD or PM direct drive

Torre quadrada de contracorrente DFN / GFN em PRFV

Células quadradas modulares que se empilham até a capacidade que a planta realmente precisa.

As torres DFN e GFN são projetos melhorados a partir dos dados de ensaio do Instituto de Projeto e Pesquisa nº 4 do Ministério de Máquinas da China.

Especificação

Tower typeSquare counter-flow, induced draft, FRP shell, modular multi-cell
Cell arrangementSingle-row or double-row multi-cell; add cells instead of oversizing one
Fan driveVariable-frequency motor or low-noise permanent-magnet direct drive
ControlTemperature-sensor driven, real-time fan adjustment
Pipe directionInlet and outlet rotatable by 90°, 180°, 270°
Water basinL — no basin · DP — shallow basin · GP — deep basin, 400 mm effective depth
Design conditionsStandard 5 °C range (D / CD) · industrial 10–25 °C (G type)
Inlet waterUp to 60 °C (higher on request)
Water qualityCirculating turbidity ≤ 50 mg/L, short term ≤ 100 mg/L
Cold resistance−50 °C; anti-icing required below −10 °C monthly average

Notas de projeto

  • Cells, not one big towerA failed cell is isolated and the plant keeps running at reduced capacity; the same cell size covers a 20 % expansion without a new tower.
  • Direct drive where noise mattersThe permanent-magnet direct-drive option removes the belt and gearbox, cutting the dominant low-frequency noise and the maintenance interval with it.
  • Three basin depthsNo basin for pit installations, shallow basin for slab mounting, 400 mm deep basin where pump suction needs the volume.
  • Rotatable connectionsInlet and outlet can be turned 90°, 180° or 270° on site, which saves a header rework when the plant room layout changes.

Opções

  • Dual-speed motor control cabinet (supplied separately)
  • Flame-retardant fill and casing option
  • Basin heater and anti-icing control
  • Stainless basin and fasteners for coastal sites

Aplicações

  • Commercial and light industrial cooling
  • District and campus condenser water
  • Plant-room roof and pit installations
  • Phased projects where cells are added over time

Mesma série

Os dados técnicos, as tabelas de desempenho e os certificados são publicados em inglês para coincidir com o documento original.English